The test setup - five fire tests with
varying room sizes and material
distributions
The TIMpuls Full-Scale Compartment Fire Tests
The following research objectives were defined for the final five TIMpuls full-acale compartment fire tests under natural fire conditions:
- Validation of the results from previous component-scale experiments in a "real test structure" under natural fire conditions:
- Influence of combustible component surfaces on fire progression
- Behavior of fire protection cladding and its protection times under natural fire exposure
- Behavior of wooden structures regarding self-extinguishment and post-fire behavior
- Extinguishability of standard construction methods in timber construction
- Analysis of fire spread through the façade to the floor above the fire floor due to combustible surfaces in the room
- Investigation of the effects of fire protection measures in the joint and connection areas of components
- Evaluation of structural stability under natural fire exposure
- Assessment of compartmentation (fire and smoke resistance, thermal insulation) under natural fire exposure
- Review and final evaluation of the current timber construction guidelines in German building regulations
Setup
T0-T2
T3-T4
Overview of the execution features of the test rooms for tests T0 to T4
Test |
T0 |
T1 |
T2 |
T3 |
T4 |
Compartment size (inside) |
4.5 m x 4.5 m x 2.4 m |
4.5m x 9.0 m x 2.4 m |
|||
Floor space |
20.25 m2 |
40.50 m2 |
|||
Fire load density |
1085 MJ/m3 |
||||
Wall 1 |
100 mm CLT |
100 mm CLT |
150 mm CLT |
140 mm LTF |
150 mm CLT |
Wall 2 |
100 mm CLT 2 x 25 mm GPF |
100 mm CLT 18 mm GF |
140 mm LTF 2 x 18 mm GF |
140 mm LTF 2 x 18 mm GF + 12 mm OSB (half wall) |
140 mm LTF 2 x 18 mm GF |
Wall 3 |
100 mm CLT 2 x 25 mm GPF |
100 mm CLT 18 mm GF |
150 mm CLT |
140 mm LTF 2 x 18 mm GF |
140 mm LTF 2 x 18 mm GPF |
Wall 4 |
100 mm CLT 2 x 25 mm GPF |
100 mm CLT 18 mm GF |
140 mm LTF 2 x 18 mm GF |
140 mm LTF 2 x 18 mm GF |
140 mm LTF 2 x 18 mm GF |
Ceiling |
180 mm GLT 2 x 25 mm GPF |
180 mm GLT |
220 mm LTF 2 x 18 mm GF |
180 mm GLT |
180 mm GLT |
Linear components |
- |
- |
- |
- |
2x Column* 1 x Beam** |
Exposed surface (initial)*** |
- |
35 % |
37 % |
42 % |
58 % |
CLT = cross-laminated timber
LTF = light timber frame
GLT = glued-laminated timber
GPF = gypsum plasterboard type F
GF = gypsum fiberboard
OSB = oriented strand board
*Column 300 × 300 mm2 GLT
**Beam 300 × 320 mm2 GLT
***As percentage of the total compartment surfaces excluding floor and window